Introduction:
1. This type of vacuum switch tube adopts one-time sealing and draining process, ceramic shell, and the contact is made of CuWC material. It has the characteristics of high insulation level, low interception value, strong arc extinguishing ability, long life, small size, simple maintenance, and no explosion hazard. , No pollution, low noise and other advantages.
2. The contactor assembled with it is used for the control and protection of the power transmission and distribution system of the electric power, machinery, chemical industry, metallurgy, mining and railway departments, especially suitable for places with frequent operations.
No. | Main Technical Specification | Type | |
TF-15.5/200-10A | |||
ELECTRIC RATINGS | |||
1 | Rated Voltage | kV | 15.5 |
2 | Rated Current | A | 200 |
3 | Rated Frequency | Hz | 50/60 |
4 | Rated Short-time(1min) Power-Frequency Withshand Voltage | kV | 60 |
5 | Circuit Resistance At Lowest Rated Contact Force | μΩ | ≤100 |
6 | Lightning Impulse Withstand Voltage | kV | 100 |
7 | Rated Short-time Withstand Current,4s | kA | 10 |
8 | Rated Peak Withstand Current | kA | 25 |
9 | Rated Short-circuit Making Current | kA | 25 |
10 | Rated Active Load Breaking Current | A | 10 |
11 | Rated Closed-loop Breaking Current | A | 200 |
LIFE | |||
1 | Mechanical Life | Times | 50000 |
3 | Storage Life | years | ≥20 |
4 | Contacts Erosion Limit | mm | 2 |
MECHANICAL DATA | |||
1 | Contact Force From Atmosphere | N | 27±8 |
2 | Counterforce of Contacts at Full Stroke | N | / |
MECHANICAL DATA OF VACUUM SWITH EQUIPPED WITH THE INTERRUPTERS | |||
1 | Contact Stroke | mm | 5±1 |
2 | Overtrave | mm | 3±1 |
3 | Average Opening Speed | m/ s | 1.1±0.2 |
4 | Average closing speed | m/ s | 0.6±0.2 |
5 | Contact Bouncing Duration at Cosing Operation | ms | ≤2 |
6 | Rated Added External Contactfinal Force | N | 260 |